Abstrakt
The paper presents a comprehensive Reliability, Availability and Maintainability (RAM) assessment of the Water Supply Plant WULS-SGGW (WSP). The Monte Carlo method was used to simulate failure events of components in the technological process of the water treatment system. BlockSim application was used to perform an analysis. The reliability block diagram was used as a system modeling method. Reliability metrics were estimated based on 1000 simulations of 15 years of operation of the station. Simulations allowed the estimation of reliability metrics for the WSP, its subsystems, sections as well as basic elements included in the model. They also made it possible to determine which components are most critical to reliability.